SINAMICS G120 功率模塊 PM 240-2 未過濾 帶集成式制動斬波器 380-480V+10/-20% 三相交流 47-63Hz 重過載功率:55kW 當 200% 3S,150% 57S, 99% 240S;環境溫度 -20 至 +50°C(HO);功率 輕過載:75kW 當 150% 3S,110% 57S, 99% 240S;環境溫度 -20 至 +40°C(LO) 708x 305x 357(高x寬x深),FSF 防護等級 IP20 不帶控制單元和 操作單元 批準從 CU 固件- 版本 V4.7 HF8
概述
PM240‑2 Power Modules – 0.55 kW to 250 kW (0.75 hp to 400 hp), IP20 degree of protection
PM240‑2 Power Modules, frame sizes FSA to FSG (with Control Unit and Operator Panel)
The PM240‑2 Power Modules are based on a new hardware platform. This permits an increase in power density as well as the application of innovative cooling concepts (push-through technology) with especially high requirements in terms of control cabinet cooling.
Furthermore, the PM240-2 Power Module is also suitable for use in safety-oriented applications. In conjunction with a fail-safe Control Unit, the drive can be transformed into a Safety Integrated Drive (see section Control Units).
The PM240‑2 Power Modules in frame sizes FSA to FSF are available both with and without an integrated line filter class A of compact design for 200 V, 400 V and 690 V line voltages (except PM240‑2 frame sizes FSD to FSF: 200 V). The PM240‑2 Power Modules in frame size FSG are available with an integrated line filter Category C3 of compact design for 400 V and 690 V line voltages, also with integrated line filter Category C2 for a line voltage of 400 V. In addition, a DC link reactor is integrated in the PM240‑2 Power Modules, frame sizes FSD to FSG, and therefore no line reactor is required.
The PM240-2 Power Modules with integrated line filter class A are suitable for connection to TN supply systems. Power Modules without integrated line filter can be connected to grounded TN/TT systems and non-grounded IT systems.
The PM240‑2 Power Module has an integrated braking chopper. In generating mode, the excess energy of the DC link can be dissipated by means of an optional braking resistor.
The permissible cable lengths between converter and motor are limited (for max. permissible cable lengths, see Integration). Longer cables can be used if output reactors are connected (see section Load-side power components).
Push-through variant
Example: PM240‑2 Power Modules, degree of protection IP20, push-through variant, frame sizes FSD to FSF (with Control Unit and Operator Panel)
The push-through variants in the frame sizes FSA to FSF allow the cooling fins of the Power Modules to be pushed through the rear panel of the control cabinet. Push-through variants should be used in applications where the amount of power loss generated inside the control cabinet itself must be minimized.
Shield plates and shield connection kits are available for use in the wiring installation of Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information, see Shield connection kits for Control Units and Power Modules in section Supplementary system components.
PM250 Power Modules – 7.5 kW to 90 kW (10 hp to 125 hp), IP20 degree of protection
PM250 Power Modules, frame sizes FSC to FSF
PM250 Power Modules are suitable for a large number of applications in general mechanical engineering. Any braking energy is directly fed back into the line supply (four-quadrant applications – a braking chopper is not required).
The PM250 Power Module features an absolutely unique technology – Efficient Infeed Technology. This feature provides the ability to feed energy back into the supply system in the generator mode (electronic braking) so that the energy is not converted into heat in a braking resistor. This saves space in the control cabinet. The time-consuming process of dimensioning the braking resistor and the expense of the extra wiring are eliminated. Furthermore, heat losses in the control cabinet are reduced.
Further, the innovative circuit design reduces the line harmonics. There is no need to use an optional line reactor at the supply infeed. This saves space and costs for engineering and procurement.
The permissible cable lengths between converter and motor are limited (for max. permissible cable lengths, see Integration). Longer cables can be used if output reactors are connected (see section Load-side power components).
Frame sizes FSD to FSF of the PM250 Power Modules are available both with as well as without integrated line filter class A.
For frame size FSC of the PM250 Power Module with an integrated line filter class A, an additional base filter of class B is available for achieving class B (see section Line-side components).
The PM250 Power Module is also designed for safety-oriented applications. In conjunction with a fail-safe Control Unit, the drive can be transformed into a Safety Integrated Drive (see section Control Units).
The PM250 Power Modules with integrated line filter class A are suitable for connection to TN supply systems. Power Modules without integrated line filter can be connected to grounded TN/TT systems and non-grounded IT systems.
Note:
Shield plates and shield connection kits are available for use in the wiring installation of Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information, see Shield connection kits for Control Units and Power Modules in section Supplementary system components.
集成
All Power Modules have the following connections and interfaces:
- PM‑IF interface to connect the Power Module to the Control Unit. The Power Module also supplies power to the Control Unit using an integrated power supply
- Motor connection using screw terminals or screw studs
- 2 PE/protective conductor connections
- Shield connection plate
Connection example for PM240‑2 Power Modules, frame sizes FSA to FSC, with or without integrated line filter
Connection example for PM240‑2 Power Modules, frame sizes FSD to FSG, with or without integrated line filter
Connection example for PM250 Power Modules with or without integrated line filter
Power and DC link components that are optionally available depending on the Power Module used
The following line-side components, DC link components and load-side power components are optionally available in the appropriate frames sizes for the Power Modules:
|
| Frame size | ||||||
|---|---|---|---|---|---|---|---|
|
| FSA | FSB | FSC | FSD | FSE | FSF | FSG |
| PM240‑2 Power Module with integrated braking chopper | |||||||
| ✓ | ✓ | ✓ | ✓ 1) | ✓ 1) | ✓ 1) | – |
| ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| – | – | – | ✓ | ✓ | ✓ | ✓ |
| Line-side components | |||||||
| Line filter class A | F | F | F | F 1) | F 1) | F 1) | – |
| Line filter class B (only for 400 V versions) | U 2) | U 2) | U 2) | – | – | – | – |
| Line filters of Category C2 or C3 (for 400 V versions frame size FSG) | – | – | – | – | – | – | I 3) |
| Line filters of Category C3 (for 690 V versions frame size FSG) | – | – | – | – | – | – | I 3) |
| Line Harmonics Filters (only for 400 V versions, frame sizes FSD to FSG) | – | – | – | S | S | S | S |
| Line reactor (only for 3 AC versions 4)) | S 5) | S 5) | S 5) | I | I | I | I |
| DC link components | |||||||
| Braking resistor | S | S | S | S | S | S | S |
| Load-side power components | |||||||
| Output reactor | S | S | S | S | S | S | S |
| Sine-wave filters (only for 400 V versions) | S | S | S | – | – | – | – |
| dv/dt filters plus VPL (only for 400 V versions) | – | – | – | S | S | S | – |
| dv/dt filters plus VPL (only for 690 V versions 8)) | – | – | – | S | S | S | S |
| PM250 Power Module with line-commutated energy recovery | |||||||
| – | – | ✓ | ✓ | ✓ | ✓ | – |
| Line-side components | |||||||
| Line filter class A | – | – | I | F | F | F | – |
| Line filter class B | – | – | U | – | – | – | – |
| Line reactor 6) | – | – | – 6) | – 6) | – 6) | – 6) | – |
| DC link components | |||||||
| Braking resistor 7) | – | – | – 7) | – 7) | – 7) | – 7) | – |
| Load-side power components | |||||||
| Output reactor | – | – | U | S | S | S | – |
| Sine-wave filter | – | – | U | S | S | S | – |
U = Base component
S = Lateral mounting
I = Integrated
F = Power Modules available with and without integrated filter class A
– = Not possible
1) The 200 V versions of the PM240‑2 Power Modules, frame sizes FSD to FSF, are only available without integrated line filter.
2) Lateral mounting is the only possible option for push-through variants.
3) The PM240‑2 Power Modules frame size FSG with an integrated Category C3 filter can also be operated on TN systems with a grounded line conductor. To do so, the grounding screw must be removed. Then Category C3 can no longer be adhered to.
4) With the appropriate wiring, the line reactors for 200 V 3 AC can be used for the 200 V versions for 200 V 1 AC. More information can be found on the internet at:
https://support.industry.siemens.com/cs/document/109486005
https://support.industry.siemens.com/cs/document/109482011
5) For frame sizes FSA to FSC, for lines with uk < 1 %, it is recommended that you use a line reactor or the next more powerful Power Module. More information can be found on the internet at:
https://support.industry.siemens.com/cs/document/109482011
6) A line reactor is not required and must not be used in conjunction with a PM250 Power Module.
7) A PM250 Power Module is capable of line-commutated energy recovery. A braking resistor cannot be connected and is not necessary.
8) The 690 V versions of the PM240‑2 Power Modules require motors with a suitable isolating system for 690 V converter operation (IVIC‑C premium). The VSD10 line with corresponding SIMOTICS GP 1LE109 General Purpose motors or SIMOTICS SD 1LE159 Severe Duty motors is ideally suited for converter operation at 690 V. Additional information is available in Catalog D 81.1.
General design information
Converter comprising a Power Module (PM), a Control Unit (CU), and base components (side view)
- If at all possible, the line filter should be mounted directly below the converter 1).
- With lateral mounting, the line-side components have to be mounted on the left side of the converter, and the load-side
components on the right side. - Braking resistors have to be mounted directly on the control cabinet wall due to heating issues.
Recommended installation combinations of the converter and optional power and DC link components
| Power Module | Base | Lateral mounting | |
|---|---|---|---|
| Frame size |
| Left of the converter | Right of the converter |
| FSA and FSB | Line filters, sine-wave filters | Line reactor | Output reactor and/or |
| FSC | Line filters 1), sine-wave filters | Line reactor | Output reactor and/or |
| FSD and FSE | – | Line filters, Line Harmonics Filters | Output reactor or |
| FSF and FSG | – | Line filters, Line Harmonics Filters | Output reactor or |
1) With the PM250 Power Module, frame size FSC, the output reactor and sine-wave filter can be installed as base components. The output reactor or sine-wave filter should be mounted under the line filter.
Maximum permissible cable lengths from the motor to the converter when using output reactors, sine-wave filters, dv/dt filters plus VPL or filters depending on the voltage range and the Power Module being used
|
| Maximum permissible motor cable lengths (shielded/unshielded) in m (ft) | ||||||
|---|---|---|---|---|---|---|---|
| Frame size | FSA | FSB | FSC | FSD | FSE | FSF | FSG |
| PM240‑2 Power Module with integrated braking chopper | |||||||
| Without optional power components |
|
|
|
|
|
|
|
| 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 200/300 (656/984) | 200/300 (656/984) | 300/450 (984/1476) | – |
| 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | – | – | – | – |
| 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 200/300 (656/984) | 200/300 (656/984) | 300/450 (984/1476) | 300/450 (984/1476) |
| 50/100 (164/328) | 100/100 1) (328/328) 1) | 150/150 1) (492/492) 1) | 200/300 (656/984) | 200/300 (656/984) | 300/450 (984/1476) | 300/450 (984/1476) |
| – | – | – | 200/300 (656/984) | 200/300 (656/984) | 300/450 (984/1476) | 300/450 (984/1476) |
| With optional output reactor |
|
|
|
|
|
|
|
| 150/225 (492/738) | 150/225 (492/738) | 150/225 (492/738) | 200/300 (656/984) 2) | 200/300 (656/984) 2) | 300/450 (984/1476) 2) | – |
| 150/225 (492/738) | 150/225 (492/738) | 150/225 (492/738) | 200/300 (656/984) 2) | 200/300 (656/984) 2) | 300/450 (984/1476) 2) | 300/450 (984/1476) 2) |
| 100/150 (328/492) | 100/150 (328/492) | 100/150 (328/492) | 200/300 (656/984) 2) | 200/300 (656/984) 2) | 300/450 (984/1476) 2) | 300/450 (984/1476) 2) |
| – | – | – | 350/525 (1148/1723) | 350/525 (1148/1723) | 525/800 (1723/2625) | 525/800 (1723/2625) |
| With optional sine-wave filter |
|
|
|
|
|
|
|
| 50/200 (164/656) | 50/200 (164/656) | 50/200 (164/656) | – | – | – | – |
| With optional dv/dt filter plus VPL |
|
|
|
|
|
|
|
| – | – | – | 30 kW: 350/525 (1148/1723) 37 kW: 450/650 (1476/2133) 3) | 450/650 (1476/2133) 3) | 450/650 (1476/2133) 3) | – |
| – | – | – | 350/525 (1148/1723) | 350/525 (1148/1723) | 450/650 (1476/2133) 3) | 450/650 (1476/2133) 3) |
| With integrated line filter According to EN 55011 to comply with radio interference emissions according to EN 61800‑3 EMC Category C2 |
|
|
|
|
|
|
|
| 50/– (164/–) | 50/– (164/–) | 50/– (164/–) | – | – | – | – |
| 50/– (164/–) | 100/– (328/–) 4) | 150/– (492/–) 4) | 150/– (492/–) | 150/– (492/–) | 150/– (492/–) | 150 /– (492/–) Category C2) 300 /– (984/–) (Category C3 5)) |
| – | – | – | 100/– (328/–) | 100/– (328/–) | 150 /– (492/–) (Category C3) | 300 /– (984/–) (Category C3 5)) |
| With optional, external line filter class B According to EN 55011 to comply with conducted radio interference emissions according to EN 61800‑3 EMC Category C1 6), together with unfiltered Power Module |
|
|
|
|
|
|
|
| 50/– (164/–) | 50/– (164/–) | 50/– (164/–) | – | – | – | – |
| With optional, external line filter class B According to EN 55011 to comply with conducted radio interference emissions according to EN 61800-3 EMC Category C2 6), together with unfiltered Power Module |
|
|
|
|
|
|
|
| 150/– (492/–) 4) | 100/– (328/–) 4) | 100/– (328/–) 4) | – | – | – | – |
| With optional, external line filter class B According to EN 55011 and optional output reactor to comply with radio interference emissions according to EN 61800‑3 EMC Category C2 6), together with unfiltered Power Module |
|
|
|
|
|
|
|
| 150/– (492/–) | 150/– (492/–) | 150/– (492/–) | – | – | – | – |
| 100/– (328/–) | 100/– (328/–) | 100/– (328/–) | – | – | – | – |
| PM250 Power Module with line-commutated energy recovery | |||||||
| Without optional power components | – | – | 25/100 (82/328) | 50/100 (164/328) 7) | 50/100 (164/328) 7) | 50/100 (164/328) 7) | – |
| With optional output reactor |
|
|
|
|
|
|
|
| – | – | 150/225 (492/738) | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | – |
| – | – | 100/150 (328/492) | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | – |
| With optional sine-wave filter |
|
|
|
|
|
|
|
| – | – | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | – |
1) The values apply with low-capacitance CY cables – the max. permissible motor cable length is 50 m (164 ft) (shielded) and 100 m (328 ft) (unshielded) as standard.
2) For frame sizes FSD to FSG the maximum permissible cable lengths are not increased with an output reactor. By means of the output reactor, the loading of the motor windings is reduced by lower rates of voltage rise (dv/dt). By means of two output reactors connected in series, the maximum permissible cable lengths for frame sizes FSD and FSE are increased to 350 m (1148 ft) (shielded) and 525 m (1723 ft) (unshielded), and for frame sizes FSF and FSG to 525 m (1723 ft) (shielded) and 800 m (2625 ft) (unshielded).
3) Maximum overvoltage at the motor terminals <1350 V with cable lengths up to 450 m (1476 ft) shielded or 650 m (2133 ft) unshielded – maximum overvoltage at the motor terminals <1500 V with cable lengths up to 525 m (1723 ft) shielded or 800 m (2625 ft) unshielded.
4) The values apply with low-capacitance CY cables - the max. permissible motor cable length is 50 m (164 ft) (shielded) as standard.
5) The 690 V versions of the PM240‑2 Power Modules frame size FSG are only available with an integrated Category C3 filter. To operate the converter also within TN systems with grounded outer conductor, you must remove the grounding screw.
6) More information is available on the internet at
/sinamics-g120/documentation
7) Max. motor cable length 25 m (82 ft) (shielded) for Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2.
技術規范
General technical specifications
| Power Modules | PM240‑2 | PM250 |
|---|---|---|
| System operating voltage | FSA ... FSC: FSD ... FSG: | 380 ... 480 V 3 AC ±10 % |
| Line supply requirements | 200 V: >25 With RSC >50 it is advisable for FSA to FSC to install a line reactor, or alternatively, to select a Power Module with the next-higher power rating. 400 V: >25 With RSC >100 it is advisable for FSA to FSC to install a line reactor, or alternatively, to select a Power Module with the next-higher power rating. 690 V: No restriction | >100 |
| Input frequency | 47 ... 63 Hz | |
| Output frequency |
| |
| 0 ... 550 Hz | |
| 0 ... 240 Hz | |
| Pulse frequency | 200 V: 4 kHz 400 V: ≤90 kW: 4 kHz; >90 kW: 2 kHz 690 V: 2 kHz For higher pulse frequencies, see derating data | 4 kHz For higher pulse frequencies, see derating data |
| Power factor λ | FSA ... FSC: FSD ... FSG: | 0.9 |
| Offset factor cos φ | FSA ... FSC: >0.96 FSD ... FSG: 0.98 ... 0.99 | 0.95 capacitive |
| Converter efficiency According to IEC 61800-9-2 | 200 V: >96.2 ... 97.1 % 400 V: >96.0 ... 98.0 % 690 V: >97.3 ... 98.2 % | 96.5 ... 97.6 % 1) |
| Efficiency class According to IEC 61800-9-2 | IE2 | IE2 1) |
| Output voltage, max. as % of input voltage | 95 % | 87 % |
| Overload capability |
| |
Note: No reduction in base-load current IL for use of overload. | 1.5 × base-load current IL (i.e. 150 % overload) for 3 s plus 1.1 × base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s | 1.5 × base-load current IL (i.e. 150 % overload) for 3 s plus 1.1 × base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s |
Note: No reduction in base-load current IH for use of overload. | 2 × base-load current IH (i.e. 200 % overload) for 3 s plus 1.5 × base-load current IH (i.e. 150 % overload) for 57 s within a cycle time of 300 s | 2 × base-load current IH (i.e. 200 % overload) for 3 s plus 1.5 × base-load current IH (i.e. 150 % overload) for 57 s within a cycle time of 300 s |
| Possible braking methods | DC braking Compound braking Dynamic braking with integrated braking chopper | Energy recovery in generator operation |
| Degree of protection | IP20 (standard or push-through) | IP20 |
| Operating temperature |
| |
| Frame sizes FSA ... FSC: Frame sizes FSD ... FSG: | 0 ... 40 °C (32 ... 104 °F) without derating |
| Frame sizes FSA ... FSC: Frame sizes FSD ... FSG: | 0 ... 50 °C (32 ... 122 °F) without derating |
| Relative air humidity | < 95 % RH, condensation not permissible | |
| Cooling | Internal air cooling, power units with increased air cooling by built-in fans | Internal air cooling, power units with increased air cooling by built-in fans |
| Installation altitude | Up to 1000 m (3281 ft) above sea level without derating, | Up to 1000 m (3281 ft) above sea level without derating, |
| Protection functions |
| |
| Short-Circuit Current Rating SCCR according to UL | 200 V: 100 kA 400 V: 100 kA 690 V: 100 kA | FSC: 40 kA FSD … FSF: 42 kA |
| Compliance with standards | CE, UKCA, cULus, RCM, SEMI F47, RoHS, EAC For frame size FSD ... FSG also: WEEE (Waste Electrical & Electronic Equipment) | CE, UKCA, UL, cUL, RCM, SEMI F47, RoHS, EAC |
| CE marking, according to | Low-Voltage Directive 2014/35/EU Ecodesign requirements of the EU Directive 2019/1781 1) EMC Directive 2014/30/EU | |
1) The SINAMICS G120 frequency converters fall under the ecodesign requirements of the EU Directive 2019/1781; however, the SINAMICS G120 frequency converters with PM250 Power Modules are considered to be frequency converters with regenerative feedback functionality. Therefore, no efficiency requirements apply in this case.
2) Applies to industrial control panel installations to NEC Article 409 or UL 508A.
PM240‑2 Power Modules standard variant
| Line voltage 200 ... 240 V 1 AC/3 AC | PM240‑2 Power Modules standard variant | |||||
|---|---|---|---|---|---|---|
| Without integrated line filter | 6SL3210-1PB13-0UL0 | 6SL3210-1PB13-8UL0 | 6SL3210-1PB15-5UL0 | 6SL3210-1PB17-4UL0 | 6SL3210-1PB21-0UL0 | |
| With integrated line filter class A | 6SL3210-1PB13-0AL0 | 6SL3210-1PB13-8AL0 | 6SL3210-1PB15-5AL0 | 6SL3210-1PB17-4AL0 | 6SL3210-1PB21-0AL0 | |
| Output current at 50 Hz 230 V 1 AC |
|
|
|
|
|
|
| A | 3.2 | 4.2 | 6 | 7.4 | 10.4 |
| A | 3.2 | 4.2 | 6 | 7.4 | 10.4 |
| A | 2.3 | 3.2 | 4.2 | 6 | 7.4 |
| A | 4.6 | 6 | 8.3 | 11.1 | 15.6 |
| Rated power |
|
|
|
|
|
|
| kW (hp) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | 2.2 (3) |
| kW (hp) | 0.37 (0.50) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) |
| Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 |
| Efficiency η According to IEC 61800-9-2 | % | >96.2 | >96.4 | >96.7 | >96.4 | >96.3 |
| Power loss 3) According to IEC 61800-9-2 | kW | 0.037 | 0.046 | 0.061 | 0.082 | 0.118 |
| Cooling air requirement | m3/s (ft3/s) | 0.005 (0.18) | 0.005 (0.18) | 0.0092 (0.32) | 0.0092 (0.32) | 0.0092 (0.32) |
| Sound pressure level L pA (1 m) | dB | <50 | <50 | <62 | <62 | <62 |
| Input current 4) |
|
|
|
|
|
|
| A | 7.5/4.2 | 9.6/5.5 | 13.5/7.8 | 18.1/9.7 | 24/13.6 |
| A | 6.6/3 | 8.4/4.2 | 11.8/5.5 | 15.8/7.8 | 20.9/9.7 |
| Line supply connection U1/L1, V1/L2, W1/L3 |
| Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector |
| mm2 | 1.5 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 |
| Motor connection U2, V2, W2 |
| Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector |
| mm2 | 1.5 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 |
| PE connection |
| Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector |
| Motor cable length, max. |
|
|
|
|
|
|
| m (ft) | 50 (164) | 50 (164) | 50 (164) | 50 (164) | 50 (164) |
| m (ft) | 100 (328) | 100 (328) | 100 (328) | 100 (328) | 100 (328) |
| Degree of protection |
| IP20 | IP20 | IP20 | IP20 | IP20 |
| Dimensions |
|
|
|
|
|
|
| mm (in) | 73 (2.87) | 73 (2.87) | 100 (3.94) | 100 (3.94) | 100 (3.94) |
| mm (in) | 196 (7.72) | 196 (7.72) | 292 (11.50) | 292 (11.50) | 292 (11.50) |
|
|
|
|
|
|
|
| mm (in) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) |
| mm (in) | 238 (9.37) | 238 (9.37) | 238 (9.37) | 238 (9.37) | 238 (9.37) |
| Frame size |
| FSA | FSA | FSB | FSB | FSB |
| Weight, approx. |
|
|
|
|
|
|
| kg (lb) | 1.4 (3.09) | 1.4 (3.09) | 2.8 (6.17) | 2.8 (6.17) | 2.8 (6.17) |
| kg (lb) | 1.6 (3.53) | 1.6 (3.53) | 3.1 (6.84) | 3.1 (6.84) | 3.1 (6.84) |
1) The rated output current IN and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the internet at:
https://support.industry.siemens.com/cs/document/
4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on IN) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.
| Line voltage 200 ... 240 V 1 AC/3 AC | PM240‑2 Power Modules standard variant | ||
|---|---|---|---|
| Without integrated line filter | 6SL3210-1PB21-4UL0 | 6SL3210-1PB21-8UL0 | |
| With integrated line filter class A | 6SL3210-1PB21-4AL0 | 6SL3210-1PB21-8AL0 | |
| Output current at 50 Hz 230 V 1 AC |
|
|
|